500 kV變壓器無勵(lì)磁分接開關(guān)放電故障診斷分析

來源:電工電氣發(fā)布時(shí)間:2024-07-02 14:02瀏覽次數(shù):305

500 kV變壓器無勵(lì)磁分接開關(guān)放電故障診斷分析

丁凱,李文燕,張翾喆,劉昌標(biāo),周杰,謝斯晗
(國(guó)網(wǎng)浙江省電力公司超高壓分公司,浙江 杭州 311232)
 
    摘 要:無勵(lì)磁分接開關(guān)出現(xiàn)放電性故障會(huì)嚴(yán)重危害變壓器安全運(yùn)行。介紹了一起 500 kV 變壓器交接試驗(yàn)過程中脈沖局部放電試驗(yàn)異常的案例,應(yīng)用脈沖電流法、特高頻法、超聲波法等多維局部放電檢測(cè)技術(shù)進(jìn)行時(shí)差定位,成功診斷了變壓器無勵(lì)磁分接開關(guān)內(nèi)部異物放電故障;通過材質(zhì)成分分析判斷異物為動(dòng)觸頭旋轉(zhuǎn)軸壓環(huán)的機(jī)加工碎屑,異物位于無勵(lì)磁分接開關(guān)動(dòng)觸頭旋轉(zhuǎn)軸位置,隨擋位切換而移動(dòng),導(dǎo)致各個(gè)擋位均可檢測(cè)到局部放電,且脈沖局部放電量隨擋位變化而變化。
    關(guān)鍵詞: 變壓器;無勵(lì)磁分接開關(guān);局部放電;脈沖電流法;特高頻法;超聲波法;時(shí)差定位;異物放電故障
    中圖分類號(hào):TM403.4     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2024)06-0049-05
 
Fault Diagnosis and Analysis of 500 kV Transformer
Non-Excitation Tap-Changer Discharge
 
DING Kai, LI Wen-yan, ZHANG Xuan-zhe, LIU Chang-biao, ZHOU Jie, XIE Si-han
(State Grid Zhejiang Electric Power Company Ultra High Voltage Branch, Hangzhou 311232, China)
 
    Abstract: The discharge failure of the non-excitation tap-changer will seriously endanger the safe operation of the transformer. In this paper, a case of abnormal pulse partial discharge test during the handover test of 500 kV transformer is introduced, and the multi-dimensional partial discharge detection technologies such as pulse current method, ultra-high frequency method, and ultrasonic method are used to locate the time difference, and the internal foreign body discharge fault of the transformer,s non-excitation tap-changer is successfully diagnosed.Through the analysis of material composition, it is judged that the foreign body is the machined debris of the rotating shaft pressure ring of the moving contact, and the foreign body is located at the position of the rotating shaft of the moving contact of the non-excitation tap-changer and moves with the gear switching, resulting in partial discharge being detected in each gear, and the amount of pulse partial discharge changes with the change of gear.
    Key words: transformer; non-excitation tap-changer; partial discharge; pulse current method; ultra-high frequency method; ultrasonic method; time difference localization; foreign body discharge fault
 
參考文獻(xiàn)
[1] 李光范,王曉寧,李鵬,等.1 000 kV 特高壓電力變壓器絕緣水平及試驗(yàn)研究[J] . 電網(wǎng)技術(shù),2008,32(3) :1-6.
[2] 陳化鋼. 電力設(shè)備預(yù)防性試驗(yàn)方法及診斷技術(shù)[M]. 北京:中國(guó)水利水電出版社,2009.
[3] 沈群武,駱賢華,陶文華,等. 變壓器現(xiàn)場(chǎng)局部放電試驗(yàn)干擾波形的判斷[J] . 浙江電力,2008,27(3) :63-65.
[4] 劉江明,沈群武,艾云飛,等. 變壓器局部放電試驗(yàn)時(shí)基于帶電檢測(cè)的異常缺陷分析[J] . 變壓器,2020,57(3) :73-77.
[5] 劉江明,孫林濤,李文燕,等. 一起 CVT 介損異常案例分析[J]. 變壓器,2019,56(7) :77-82.
[6] 劉興華,李藍(lán)翔,劉濤,等. 變壓器局部放電帶電檢測(cè)技術(shù)與故障案例分析[J] . 變壓器,2019,56(5) :72-76.
[7] 郭雪婷. 變壓器局部放電研究綜述[J] . 電聲技術(shù),2022,46(2) :114-117.
[8] 王國(guó)利,鄭毅,郝艷捧,等. 用于變壓器局部放電檢測(cè)的超高頻傳感器的初步研究[J] . 中國(guó)電機(jī)工程學(xué)報(bào),2002,22(4) :154-160.