一二次深融柱上開關斷口絕緣試驗方法研究

來源:電工電氣發(fā)布時間:2024-08-01 14:01瀏覽次數(shù):288

一二次深融柱上開關斷口絕緣試驗方法研究

趙贏峰,劉彬,呂瑋,羅運祥,孫超,石巍,方太勛
(南京南瑞繼保電氣有限公司,江蘇 南京 211100)
 
    摘 要:斷口絕緣試驗是一二次深融柱上開關(柱開)的基礎試驗項目之一。根據(jù)試品電容和雜散電容分布拓撲獲取機構箱殼體理論電位,開展了機構箱殼體電位和絕緣墊閃絡電壓測試,并采用改進措施進行斷口絕緣測試。結果表明:進線側加壓時,機構箱殼體電位大于出線側加壓工況,印證了斷口試驗擊穿現(xiàn)象;機構箱殼體電位實測值和理論值相近;絕緣墊在點臟污時絕緣性能最差,閃絡電壓為干凈狀態(tài)的37%;根據(jù)絕緣墊厚度和臟污程度調整機構箱放置位置,斷口絕緣試驗通過。一二次深融柱開斷口絕緣試驗時,需關注機構箱殼體電位,防止殼體對地放電干擾試驗結果。
    關鍵詞: 深融柱上開關;斷口絕緣;機構箱殼體;電位;雜散電容;閃絡
    中圖分類號:TM564     文獻標識碼:A     文章編號:1007-3175(2024)07-0068-05
 
Research on Test Method of the Fracture Insulation on the Primary and
Secondary Deep Melt Pole-Mounted Switch
 
ZHAO Ying-feng, LIU Bin, LYU Wei, LUO Yun-xiang, SUN Chao, SHI Wei, FANG Tai-xun
(NR Electric Co., Ltd, Nanjing 211100, China)
 
    Abstract: The fracture insulation test is one of the basic test items of the primary and secondary deep melt pole-mounted switch (pole opening). In this paper, the theoretical potential of the mechanism box shell is obtained according to the distribution topology of sample capacitance and stray capacitance, and the flashover voltage test of the mechanism box shell and the insulating pad is carried out, and the fracture insulation test is carried out by using improved measures. The results show that, when the inlet side is pressurized, the potential of the casing of the mechanism box shell is greater than that of the outlet side, which confirms the breakdown phenomenon of the fracture test.The measured potential value of the mechanism box shell is similar to the theoretical value. The insulation pad has the worst insulation performance when it is dirty, and the flashover voltage is 37% of the clean state. According to the thickness of the insulation pad and the degree of dirt to adjust the placement position of the mechanism box shell, the fracture insulation test passed. In the fracture insulation test of the of the primary and secondary deep melt pole-mounted switch, it is necessary to pay attention to the potential of the shell of the mechanism box shell to prevent the shell from interfering with the test results by the discharge to the ground.
    Key words: deep melt pole-mounted switch; fracture insulation; mechanism box shell; potential; stray capacitance; flashover
 
參考文獻
[1] 李澍森,孫志英.12 kV 配電柱上開關一二次融合關鍵技術之交流電壓傳感器[J].高電壓技術,2019,45(9) :2818-2826.
[2] 戴冬云,顧曉東,付魯軍,等.一二次深度融合柱上開關用 EVT 就地采集模塊的研究[J].高壓電器,2023,59(9) :301-311.
[3] 王東芳, 陶飛達, 黃智鵬,等.一二次融合柱上開關控制可靠性模型與優(yōu)化設計[J].高壓電器,2023,59(3) :86-92.
[4] 張小勇,賈濤,王韻,等.特高壓電器設備絕緣試驗技術研究[J].高壓電器,2007,43(2) :106-108.
[5] 李華良,孫敏,龐明明,等.中壓交流金屬封閉開關設備絕緣試驗中難點問題探析[J].電工電氣,2019(10) :61-66.
[6] 錢立驍,陳慎言.12~24 kV 氮氣絕緣環(huán)網(wǎng)柜的研制[J].高電壓技術,2014,40(12) :3717-3724.
[7] 趙贏峰,呂瑋,楊兵,等.535 kV 混合式直流斷路器端間操作沖擊電壓試驗研究[J].高電壓技術,2020,46(8) :2684-2691.
[8] 王文杰,趙贏峰,許元震,等.500 kV 快速開關型故障限流器的罐式快速開關[J].高電壓技術,2023,49(2) :803-811.
[9] 呂瑋,劉云飛,周啟文,等.多斷口快速開關型高壓故障限流器[J].電力系統(tǒng)自動化,2019,43(23) :234-239.
[10] 李興旺,劉軍,劉夢娜.一起氣體絕緣金屬封閉開關設備懸浮放電缺陷分析[J].高壓電器,2015,51(10) :205-208.
[11] 王克峰, 孫慶生, 江和順,等.一起 500 kV 變壓器穩(wěn)釘懸浮放電故障的診斷與分析[J].高壓電器,2012,48(3) :95-98.
[12] 楊勇,曹俊平,江航,等.110 kV 交聯(lián)聚乙烯電纜終端懸浮電位缺陷試驗[J].絕緣材料,2019,52(5) :59-64.