Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁(yè) >> 文章檢索 >> 往年索引

某220 kV智能變電站主變間隙保護(hù)誤動(dòng)分析

來(lái)源:電工電氣發(fā)布時(shí)間:2018-09-13 10:13 瀏覽次數(shù):679
某220 kV智能變電站主變間隙保護(hù)誤動(dòng)分析
 
陳軍1,張路2,崔大林3,南東亮2,陳龍2
(1 國(guó)網(wǎng)新疆電力有限公司吐魯番供電公司,新疆 吐魯番 838000;2 國(guó)網(wǎng)新疆電力有限公司電力科學(xué)研究院,新疆 烏魯木齊 830011;
3 國(guó)網(wǎng)新疆電力有限公司電力調(diào)度控制中心,新疆 烏魯木齊 830011)
 
    摘 要:通過(guò)對(duì)某220 kV智能變電站主變保護(hù)誤動(dòng)事故進(jìn)行分析,得出影響保護(hù)誤動(dòng)的因素:一是專業(yè)人員對(duì)設(shè)備的原理和處理方法缺乏了解,現(xiàn)場(chǎng)難以發(fā)現(xiàn)一些隱性故障;二是在設(shè)備檢修過(guò)程中,對(duì)安全措施的制定方法和程度難以準(zhǔn)確掌握,容易人為造成隱性故障。指出運(yùn)行及檢修人員要深入了解智能變電站技術(shù),提高繼電保護(hù)運(yùn)行可靠性,準(zhǔn)確隔離電網(wǎng)故障。
    關(guān)鍵詞:繼電保護(hù);非全相運(yùn)行;中性點(diǎn)間隙保護(hù);故障分析
    中圖分類號(hào):TM774     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2018)09-0038-04
 
Analysis of Main Transformer Gap Protection Malfunction in Certain 220 kV Smart Substation
 
CHEN Jun1, ZHANG Lu2, CUI Da-lin3, NAN Dong-liang2, CHEN Long2
(1 Tulufan Electric Power Supply Company of State Grid Xinjiang Power Company, Tulufan 838000, China;
2 Electric Power Research Institute of State Grid Xinjiang Power Company, Urumqi 830011 , China;
3 Electric Power Dispatching and Communication Center of State Grid Xinjiang Power Company, Urumqi 830011 , China)
 
    Abstract: Based on the analysis of main transformer protection malfunction accident in certain 220 kV smart substation, it is concluded that there were two main factors to affect on protection malfunction. On the one hand, the specialized persons did not know the principles and methods of the equipment, and it was hard to find some hidden faults at the scene, on the other hand, in the process of equipment maintenance, the method and degree of safety measures were difficult to be accurately mastered, and it was easy to cause man-made hidden faults. It is pointed out that the operation and maintenance personnel should have in-depth knowledge of smart substation technology to improve the operation reliability of relay protection.
    Key words: relay protection; open-phase operation; gap protection of transformer neutral point; fault analysis
 
參考文獻(xiàn)
[1] 樊陳,倪益民,申洪,等. 中歐智能變電站發(fā)展的對(duì)比分析[J]. 電力系統(tǒng)自動(dòng)化,2015,39(16):1-7.
[2] 王建華,張國(guó)鋼,耿英三,等. 智能電器最新技術(shù)研究及應(yīng)用發(fā)展前景[J]. 電工技術(shù)學(xué)報(bào),2015,30(9):1-11.
[3] 王同文,謝民,孫月琴,等. 智能變電站繼電保護(hù)系統(tǒng)可靠性分析[J]. 電力系統(tǒng)保護(hù)與控制,2015,43(6):58-66.
[4] 馬濤,武萬(wàn)才,馮毅. 智能變電站繼電保護(hù)設(shè)備的運(yùn)行和維護(hù)[J]. 電氣技術(shù),2015,16(6):130-131.
[5] 林耀洲, 陳秀娟, 陳維江, 等.110 和220 kV不接地運(yùn)行變壓器中性點(diǎn)保護(hù)方式[J]. 電網(wǎng)技術(shù),2012,36(4):256-259.
[6] 謝永勝,孫偉,方偉華,等.110 kV主變壓器間隙保護(hù)的整定及運(yùn)行研究[J]. 電力系統(tǒng)保護(hù)與控制,2009,37(1):96-97.
[7] 武萬(wàn)才,宋仕軍,張曉磊. 主變壓器中性點(diǎn)間隙擊穿零序保護(hù)誤動(dòng)分析與建議[J]. 電力系統(tǒng)自動(dòng)化,2012,36(14):90-94.
[8] 晏青,陳軍,梁靜,等. 變壓器中性點(diǎn)間隙零序過(guò)流保護(hù)改進(jìn)[J]. 電力科學(xué)與工程,2015,31(8):14-19.