一起特高壓變電站110 kV站用變異常調(diào)壓改進(jìn)措施分析
常騰飛,劉杰,豆寶
(國網(wǎng)浙江省電力有限公司檢修分公司,浙江 杭州 311232)
摘 要:介紹了某特高壓變電站站用交流系統(tǒng)和高壓站用變有載調(diào)壓原理,闡述了一起高壓站用變異常調(diào)壓現(xiàn)象,分析了其產(chǎn)生原因,并給出了5 種改進(jìn)措施。指出當(dāng)站外備用電源電壓超出合格范圍后,還是無法進(jìn)行電壓控制,只能使備用電源對(duì)側(cè)站盡量確保相關(guān)35 kV 母線電壓在合格范圍內(nèi),或者將本站0號(hào)站用變改造成有載調(diào)壓方式。
關(guān)鍵詞:站用變;有載調(diào)壓;特高壓變電站
中圖分類號(hào):TM63 文獻(xiàn)標(biāo)識(shí)碼:B 文章編號(hào):1007-3175(2019)06-0037-04
Discussion on Improvement Measures of Abnormal Voltage Regulation for 110 kV Station in UHV Substation
CHANG Teng-fei, LIU Jie, DOU Bao
(Maintenance Company of State Grid Zhejiang Electric Power Company, Hangzhou 311 232, China)
Abstract: This paper introduced the principle of on-load voltage regulation for the AC system and high voltage station of certain UHV substation, expounded a case of abnormal voltage regulation phenomenon in high voltage station, analyzed the produced reason and gave five kinds of improved measures. It is pointed out that after the standby power supply voltage outside the station exceeds the qualified range, the voltage control cannot be performed. It is only possible to make the standby power supply side station try to ensure that the relevant 35 kV bus voltage is within the qualified range, or changes No. 0 station in home station into an on-load voltage regulation mode.
Key words: station variable; on-load voltage regulation; UHV substation
參考文獻(xiàn)
[1] 陳強(qiáng),潘建亞. 特高壓變電站站用電系統(tǒng)設(shè)計(jì)與運(yùn)維[J]. 電力學(xué)報(bào),2017,32(1):28-34.
[2] 查申森,鄭建勇,胡繼軍. 一級(jí)降壓站用電系統(tǒng)在特高壓變電站中的應(yīng)用[J]. 電力建設(shè),2012,33(5):32-36.
[3] 吳建輝,孫軍鵬,王峰. 變壓器有載調(diào)壓二次回路探討與研究[J]. 變壓器,2012,49(11):71-72.
[4] 付文竹. 主變壓器有載調(diào)壓控制回路的改進(jìn)與完善[J]. 繼電器,2008,36(4):79-80.