Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 文章瀏覽排名

基于絕對(duì)法檢測變壓器套管在線監(jiān)測技術(shù)研究與典型應(yīng)用

來源:電工電氣發(fā)布時(shí)間:2020-01-19 14:19 瀏覽次數(shù):1103
基于絕對(duì)法檢測變壓器套管在線監(jiān)測技術(shù)研究與典型應(yīng)用
 
王偉平
(廣東電網(wǎng)有限責(zé)任公司中山供電局,廣東 中山 528400)
 
    摘 要:介紹了一種基于絕對(duì)法應(yīng)用于變壓器套管在線監(jiān)測實(shí)用技術(shù),闡述了在線監(jiān)測技術(shù)原理,并就現(xiàn)場應(yīng)用的關(guān)鍵技術(shù)提出了具體方案和建議。結(jié)合一起變壓器套管缺陷實(shí)例,通過建立等值電路簡化模型,并從理論計(jì)算上分析認(rèn)為由于主變110 kV側(cè)B相套管末屏滲油,滲油支路對(duì)在線監(jiān)測系統(tǒng)測量回路存在分流導(dǎo)致其介損數(shù)據(jù)出現(xiàn)異常,由此表明該項(xiàng)技術(shù)可作為停電預(yù)試檢測的補(bǔ)充,實(shí)時(shí)在線監(jiān)測變壓器套管絕緣狀況,提高設(shè)備安全運(yùn)行水平。
    關(guān)鍵詞:套管;在線監(jiān)測;技術(shù)研究;典型應(yīng)用
    中圖分類號(hào):TM216     文獻(xiàn)標(biāo)識(shí)碼:A     文章編號(hào):1007-3175(2020)01-0049-04
 
Research and Typical Application of On-Line Monitoring Technology for Transformer Bushing
Based on Absolute Method Detection
 
WANG Wei-ping
(Zhongshan Power Supply Bureau of Guangdong Power Grid Corp, Zhongshan 528400, China)
 
    Abstract: Introduction was made to a kind of on-line monitoring operative technology, based on absolute method detection, applied to the transformer bushing.This paper expounded the principle of on-line monitoring technology and put forward specific plans and suggestions for the key technology of field application.Combining with an example of transformer bushing defect, this paper simplified a equivalent circuit model and theoretically analyzed that the dielectric loss data of on-line monitoring system was abnormal due to the oil leakage from the end shield of B-phase bushing on 11 0 kV side of the main transformer and the diversion of the oil leakage branch to the measuring circuit of the on-line monitoring system, which indicates that the technique can be used as a supplement for preventive testing to carry out real-time online monitoring of transformer bushing insulation, so as to improve the level of equipment safe operation.
    Key words: bushing; on-line monitoring; technical study; typical application
 
參考文獻(xiàn)
[1] 李國慶,莊重,王振浩. 電容型電氣設(shè)備介質(zhì)損耗角的在線監(jiān)測[J]. 電網(wǎng)技術(shù),2007,31(7):55-58.
[2] 嚴(yán)璋. 電氣絕緣在線檢測技術(shù)[M]. 西安:西安水利電力出版社,1995.
[3] 陳維榮,宋永華,孫錦鑫. 電力系統(tǒng)設(shè)備狀態(tài)監(jiān)測的概念及現(xiàn)狀[J]. 電網(wǎng)技術(shù),2000,24(11):12-17.
[4] 林建龍,鄧敏,林力輝. 高壓絕緣設(shè)備在線監(jiān)測系統(tǒng)[J]. 電網(wǎng)技術(shù),2002,26(1):86-88.
[5] 史保壯,楊莉,王紅斌,等. 總線式變電站絕緣在線監(jiān)測系統(tǒng)的研究[J]. 電網(wǎng)技術(shù),2001,25(4):36-39.
[6] 李天云,袁明哲,彭文. EMD在變壓器介質(zhì)損耗角檢測中的應(yīng)用[J]. 中國電力,2011,44(2):23-26.
[7] 蘇陳云,黃震. 特高壓電容式電壓互感器介損和電容測量方法分析[J]. 中國電力,2012,45(4):38-41.
[8] 馬繼先,李韻,劉少宇,等. 變壓器絕緣tanδ測量中溫度影響分析[J]. 中國電力,2010,43(4):45-48.
[9] 嚴(yán)玉婷,文習(xí)山,陳巧勇,等. 雙極性過零比較法在線監(jiān)測絕緣介質(zhì)損耗角[J]. 高電壓技術(shù),2004,30(2):34-36.
[10] 蔡國雄,甄為紅,楊曉洪,等. 測量介質(zhì)損耗的數(shù)字化過零點(diǎn)電壓比較法[J]. 電網(wǎng)技術(shù),2002,26(7):15-18.
[11] 馬為民,吳維韓.tanδ數(shù)字測量中過零比較法的應(yīng)用[J]. 高壓電器,1996,32(1):25-28.
[12] 左自強(qiáng),徐陽,曹曉瓏,等. 計(jì)算電容型設(shè)備介質(zhì)損耗因數(shù)的相關(guān)函數(shù)法的改進(jìn)[J]. 電網(wǎng)技術(shù),2004,28(18):53-57.
[13] 龍鋒,王富榮,李大進(jìn),等. 容性設(shè)備介質(zhì)損耗因數(shù)在線監(jiān)測方法及誤差分析研究[J]. 電力科學(xué)與工程,2004(2):19-21.
[14] 陳石楨,施廣宇,張孔林. 變壓器套管在線監(jiān)測方法探討[J]. 電工電氣,2013(6):1-6.
[15] 趙亮,李燕青. 提高介損角測量準(zhǔn)確性的濾波新算法[J]. 中國電力,2013,46(7):57-60.