Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁(yè) >> 文章檢索 >> 往年索引

高壓直流輸電工程噪聲濾波器性能評(píng)估

來(lái)源:電工電氣發(fā)布時(shí)間:2021-04-30 14:30 瀏覽次數(shù):731

高壓直流輸電工程噪聲濾波器性能評(píng)估

魏綱,王典浪,曹鴻,李國(guó)艮
(中國(guó)南方電網(wǎng)有限責(zé)任公司超高壓輸電公司曲靖局,云南 曲靖 655000)

 

    摘 要:近年來(lái)高壓直流輸電系統(tǒng)換流站交流 PLC 濾波器故障時(shí)有發(fā)生,為查明故障原因,對(duì) ±500 kV 溪洛渡直流輸電工程送端昭通換流站交流 PLC 濾波器的配置方案、濾波性能和定值計(jì)算情況進(jìn)行了研究。發(fā)現(xiàn)對(duì)該工程交流 PLC 濾波器性能研究及參數(shù)選型時(shí),應(yīng)力定值計(jì)算僅考慮了電抗器、調(diào)諧單元等附屬元件承受最大穩(wěn)態(tài)電壓和電流應(yīng)力需求,未考慮在弱交流系統(tǒng)甚至孤島運(yùn)行下交流 PLC 濾波器在直流操作及各類典型故障過(guò)程承受的暫態(tài)諧波電流電壓應(yīng)力情況,結(jié)合該工程某次直流緊急停運(yùn)過(guò)程中發(fā)現(xiàn)交流 PLC 濾波器調(diào)諧單元承受的實(shí)際諧波電流應(yīng)力顯著超過(guò)其設(shè)計(jì)額定值,說(shuō)明該設(shè)備存在較大安全隱患。針對(duì)高壓直流換流站交流 PLC 噪聲濾波器的設(shè)計(jì)選型、隱患設(shè)備評(píng)估整治等提出了相應(yīng)的建議措施,具有一定借鑒意義。
    關(guān)鍵詞:PLC 濾波器;調(diào)諧單元;暫態(tài)諧波;定值計(jì)算;設(shè)計(jì)選型;畸變應(yīng)力
    中圖分類號(hào):TM721.1     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2021)04-0030-04
 
Performance Evaluation of Noise Filter for HVDC Transmission Project
 
WEI Gang, WANG Dian-lang, CAO Hong, LI Guo-gen
(Qujing Bureau of China Southern Power Grid EHV Power Transmission Company, Qujing 655000, China)
 
    Abstract: In recent years, failures of AC PLC filters in HVDC converter stations have occurred from time to time. In order to find out the causes of these failures, the configuration scheme, filtering performance and constant value calculation of AC PLC filters in Zhaotong converter station of 500 kV Xiluodu HVDC transmission project are studied, it is found that the maximum steady state voltage and current stress of auxiliary components such as reactor and tuning unit are only taken into account in the stress setting calculation when the AC PLC filter is studied and its parameters are selected, not considering the transient harmonic current and voltage stress of AC PLC filter under DC operation and typical fault process in weak AC system or even isolated island. Combined with the DC emergency shutdown process of this project,it is found that the actual harmonic current stress of the AC PLC filter tuning unit is much higher than its design rating, which shows that the equipment has great hidden trouble. Finally, some suggestions are put forward for the design and selection of AC PLC noise filter in HVDC converter station, as well as the renovation of hidden trouble equipment.
    Key words: PLC filter; tuning unit; transient harmonic; setting calculation; type selection; distortion stress
 
參考文獻(xiàn)
[1] 李勇,羅隆福,賀達(dá)江,等. 新型直流輸電系統(tǒng)典型諧波分布特性分析[J] . 電力系統(tǒng)自動(dòng)化,2009,33(10) :59-63.
[2] 鄭勁,文俊,石巖,等. 特高壓直流輸電直流側(cè)高頻干擾及濾波器型式[J] . 高電壓技術(shù),2006,32(12) :174-177.
[3] 趙婉君. 高壓直流輸電工程技術(shù)[M] . 北京:中國(guó)電力出版社,2007.
[4] 劉振亞. 特高壓直流輸電技術(shù)研究成果專輯[M] .北京:中國(guó)電力出版社,2006.
[5] 夏道止,沈贊塤. 高壓直流輸電系統(tǒng)的諧波分析及濾波[M]. 北京:水利電力出版社,1993.
[6] 南方電網(wǎng)科學(xué)研究院.CSG/YG Ⅲ /ED1.831.ZC-0_ 溪洛渡右岸電站送電廣東±500 kV 同塔雙回直流輸電工程交/ 直流 PLC 噪聲濾波器研究報(bào)告[R]. 廣州:南方電網(wǎng)科學(xué)研究院,2011.
[7] 南方電網(wǎng)科學(xué)研究院.CSG/YG Ⅲ /ED3.421.Z-0_ 溪洛渡右岸電站送電廣東±500 kV 同塔雙回直流輸電工程交流 PLC 濾波器設(shè)備規(guī)范[R] . 廣州:南方電網(wǎng)科學(xué)研究院,2011.
[8] 孫中明. 葛南直流濾波器性能研究[J] . 高電壓技術(shù),2004,30(11) :65-66.
[9] 劉洪濤,文俊. 葛—上直流輸電工程直流濾波器校核計(jì)算[C]// 中國(guó)電工技術(shù)學(xué)會(huì)2004 年( 第一屆)電工技術(shù)前沿問(wèn)題學(xué)術(shù)論壇,2004 :100-103.
[10] 楊金根,馬為民. 靈寶換流站交流濾波器性能研究[J]. 高電壓技術(shù),2004,30(11) :60-62.
[11] 黃成,黎小林,任軍輝,等. 糯扎渡±800 kV 直流輸電工程交/ 直流 PLC 噪聲濾波器研究[J] . 高壓電器,2014,50(8) :87-92.
[12] 南方電網(wǎng)科學(xué)研究院.CSG/YG Ⅲ /ED1.070.ZC-0_ 溪洛渡右岸電站送電廣東±500 kV 同塔雙回直流輸電工程暫態(tài)電流要求研究報(bào)告[R] . 廣州:南方電網(wǎng)科學(xué)研究院,2011.
[13] 南方電網(wǎng)科學(xué)研究院.CSG/YG Ⅲ /ED1.919.ZC-0_ 低次諧波諧振研究報(bào)告[R] . 廣州:南方電網(wǎng)科學(xué)研究院,2011.
[14] 劉方,周耀顯,張予洛. 紅外測(cè)溫技術(shù)在電容式電壓互感器故障判斷中的應(yīng)用[J] . 電力電容器與無(wú)功補(bǔ)償,2011,32(1) :50-53.