Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 往年索引

10 kV戶外柱上斷路器容量性能試驗的關(guān)鍵點(diǎn)及控制措施

來源:電工電氣發(fā)布時間:2022-09-26 14:26 瀏覽次數(shù):397

10 kV戶外柱上斷路器容量性能試驗的關(guān)鍵點(diǎn)及控制措施

李嘯,李釗,劉德宇,顧曉賀
(常州博瑞電力自動化設(shè)備有限公司,江蘇 常州 213025)
 
    摘 要:對帶隔離開關(guān)的戶外柱上斷路器而言,容量性能試驗要求為過程中不能發(fā)生真空滅弧室觸頭和隔離開關(guān)觸頭打火或熔焊現(xiàn)象。從真空滅弧室觸頭的選型、斷路器機(jī)械特性參數(shù)的調(diào)試、隔離開關(guān)觸頭形式的選擇、隔離開關(guān)觸頭壓力的調(diào)校四個方面,通過多次容量性能試驗的摸底測試,分別提出了真空滅弧室觸頭采用杯狀縱磁結(jié)構(gòu)觸頭,機(jī)械特性調(diào)試參數(shù)滿足滅弧室的技術(shù)參數(shù),隔離開關(guān)觸頭采用線接觸形式,及隔離開關(guān)觸頭壓力值控制在(185±25) N 的技術(shù)關(guān)鍵點(diǎn),并對真空滅弧室的生產(chǎn)和隔離開關(guān)觸頭的壓力值也提出了控制措施,為柱上斷路器的器件選型、關(guān)鍵工藝控制、質(zhì)量管控等提供了參考。
    關(guān)鍵詞: 柱上斷路器;隔離開關(guān);容量性能試驗;特性參數(shù);觸頭壓力
    中圖分類號:TM561     文獻(xiàn)標(biāo)識碼:B     文章編號:1007-3175(2022)09-0046-05
 
Key Points and Control Measures of Capacity Performance Test of the
10 kV Outdoor Pole-Mounted Circuit Breaker
 
LI Xiao, LI Zhao, LIU De-yu, GU Xiao-he
(Changzhou Boil Electric Power Automation Equipments Co., Ltd, Changzhou 213025, China)
 
    Abstract: For an outdoor pole-mounted circuit breaker with isolating switch, test requirements are that the contact of vacuum interrupter and isolating switch cannot be ignited or fused.This paper discussed the selection of vacuum interrupter contacts, the adjustment of the mechanical characteristic parameter of the circuit breaker, the contact types of the disconnector selection, and the adjustment of the contact pressure of the disconnector. Based on the capacity performance test this study proposed four suggestions: the contact of vacuum interrupter should use cupshaped longitudinal magnetic structure, the adjustment parameters of mechanical characteristics have to meet the technical parameters of arc interrupter, the isolating switch uses the line contact form, and the (185±25) N is the technical point of the contact pressure of isolating switch.In addition, this paper proposed the control measures for the production of the vacuum interrupter and the pressure value of the contact of the isolating switch. It provides a reference for the component selection of the pole-mounted circuit breaker, the key-process control and the quality control of the pole-mounted circuit breaker, etc.
    Key words: pole-mounted circuit breaker; isolating switch; capacity performance test; characteristic parameter; contact pressure
 
參考文獻(xiàn)
[1] 李靜,谷禹.10 kV 戶外柱上斷路器短路開斷試驗中一體式隔離開關(guān)觸頭燒蝕影響分析[J] . 設(shè)備研制與應(yīng)用,2017,34(12):66-70.
[2] 全國高壓開關(guān)設(shè)備標(biāo)準(zhǔn)化技術(shù)委員會. 高壓交流斷路器:GB 1984—2014[S]. 北京:中國標(biāo)準(zhǔn)出版社,2014:43.
[3] 全國高壓開關(guān)設(shè)備標(biāo)準(zhǔn)化技術(shù)委員會. 高壓交流隔離開關(guān)和接地開關(guān):GB 1985—2014[S] . 北京:中國標(biāo)準(zhǔn)出版社,2014:20-22.
[4] 李剛,高享想,劉浩軍,等. 高壓交流斷路器大容量短路開斷與關(guān)合試驗技術(shù)[J] . 高壓電器,2018,54(2):68-75.
[5] 盛民學(xué),王志清. 戶外高壓隔離開關(guān)常見故障的原因分析處理[J] . 高壓電器,2010,46(10):93-96.
[6] 胡紅光. 隔離開關(guān)觸頭結(jié)構(gòu)與發(fā)熱原因分析[J] .高電壓技術(shù),2001,27(5):72-75.
[7] 宋輝,劉順新. 真空開關(guān)電弧的研究分析[J] . 電氣制造,2013(10):28-31.
[8] 游一民,歐陽振國,馬平,等. 影響真空斷路器關(guān)合時觸頭熔焊的另一重要因素[J] . 高壓電器,2014,50(8):53-56.
[9] 姜生,李世民,王繼元. 真空斷路器機(jī)械特性的探討[J]. 高壓電器,2002,38(4):61-64.
[10] 沈佩琦,李為民,周友東.10 kV 戶外柱上開關(guān)存在的問題及對策[J]. 高壓電器,2017,53(4):211-214.