高壓六氟化硫斷路器觸頭間動(dòng)態(tài)擊穿特性試驗(yàn)研究
夏亞龍,林莘,徐建源,蘇安,王飛鳴
(沈陽(yáng)工業(yè)大學(xué) 電氣工程學(xué)院,遼寧 沈陽(yáng) 110870)
摘 要:針對(duì)六氟化硫(SF6)氣體在高壓電器設(shè)備實(shí)際形狀電極間的擊穿特性,搭建126 kV SF6斷路器觸頭間動(dòng)態(tài)擊穿特性試驗(yàn)回路,分別測(cè)量斷路器在不同電壓極性和滅弧室充氣壓強(qiáng)下分、合閘過(guò)程中觸頭間擊穿電壓,統(tǒng)計(jì)試驗(yàn)擊穿點(diǎn)電壓值和對(duì)應(yīng)的開(kāi)距,分別采用冪函數(shù)、四次多項(xiàng)式對(duì)分、合閘過(guò)程觸頭間擊穿點(diǎn)電壓值進(jìn)行擬合,得到不同開(kāi)距下?lián)舸╇妷簲M合曲線,并給出觸頭間擊穿電壓與開(kāi)距之間的數(shù)學(xué)表達(dá)式。試驗(yàn)結(jié)果表明:SF6斷路器分、合閘過(guò)程中,當(dāng)觸頭間開(kāi)距達(dá)到一定值后,SF6氣體表現(xiàn)出“反極性”效應(yīng);同一開(kāi)距下,分閘過(guò)程(平均速度9.6 m/s)擊穿電壓小于合閘過(guò)程(平均速度4.7 m/s)。
關(guān)鍵詞:六氟化硫;高壓斷路器;擊穿電壓
中圖分類(lèi)號(hào):TM561.3 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1007-3175(2016)04-0007-05
Experimental Study on Dynamic Breakdown Characteristics of Gap Between Contacts for High-Voltage SF6 Circuit Breaker
XIA Ya-long, LIN Xin, XU Jian-yuan, SU An, WANG Fei-ming
(School of Electrical Engineering, Shenyang University of Technology, Shenyang 110870, China)
Abstract: For the breakdown characteristics of SF6 medium between the real shape electrodes for high-voltage electrical equipment, this paper set up the experimental circuit of dynamic breakdown characteristics of gap between contacts for 126 kV SF6 circuit breaker. The breakdown voltages were measured during the process of circuit breakers breaking and closing under different voltage polarity and arc extinguish chamber air inflation pressure respectively. Voltage value and corresponding opening travel of experimental breakdown point were recorded. The fitting curves of breakdown voltage under different opening travel were obtained by using power function and four order polynomial to fit the breakdown voltage value of breaking and closing process respectively. This paper gave the mathematical expression of breakdown voltage and distance between the contacts. The test results show that during the process of SF6 circuit breakers breaking and closing, the positive polarity breakdown voltage is greater than negative polarity of SF6 gas when the opening travel reaches a certain value and the breakdown voltage of breaking process (the average speed is 9.6 m/s) is lower than that of closing process (the average speed is 4.7 m/s) for the same contact gap.
Key words: sulfur hexafluoride; high-voltage circuit breaker; breakdown voltage
參考文獻(xiàn)
[1] 林莘.現(xiàn)代高壓電器技術(shù)[M].2版.北京:機(jī)械工業(yè)出版社,2011.
[2] 劉振亞.中國(guó)特高壓交流輸電技術(shù)創(chuàng)新[J].電網(wǎng)技術(shù),2013,37(3):566-574.
[3] 鐘建英.高壓自能式SF6斷路器滅弧室內(nèi)耦合場(chǎng)的仿真與分析[D].沈陽(yáng):沈陽(yáng)工業(yè)大學(xué),2006.
[4] 嚴(yán)璋,朱德恒.高電壓絕緣技術(shù)[M].2版.北京:中國(guó)電力出版社,2002.
[5] Luque A, Ebert U,Montijn C, et al. Photoionization in negative streamers:fast computations and two propagation modes[J].Applied Physics Letters,2007,90(8):1-4.
[6] Georghiou G E,Papadakis A P,Morrow R,et al.Numerical modeling of atmospheric pressure gas discharges leading to plasma production[J].Journal of Physics D:Applied Physics,2005,38(20):303-328.
[7] 楊茜,榮命哲,吳翊,等.低壓斷路器中空氣電弧重?fù)舸┈F(xiàn)象的仿真與實(shí)驗(yàn)研究[J].中國(guó)電機(jī)工程學(xué)報(bào),2007,27(6):84-88.
[8] 程顯,段雄英,廖敏夫,等.混合斷路器大電流開(kāi)斷過(guò)程中真空電弧與SF6電弧相互作用的仿真[J].高電壓技術(shù),2012,38(6):1529-1536.
[9] 魏俊梅.800 kV SF6高壓斷路器的研究與開(kāi)發(fā)[D].沈陽(yáng):沈陽(yáng)工業(yè)大學(xué),2008.
[10] 劉振亞.中國(guó)電力與能源[M].北京:中國(guó)電力出版社,2012.
[11] 李鑫濤,林莘,徐建源,等.基于FEM-FCT法的均勻電場(chǎng)下SF6氣體擊穿特性[J].高電壓技術(shù),2014,40(10):3046-3053.
[12] 趙虎,李興文,賈申利.SF6及其混合氣體臨界擊穿場(chǎng)強(qiáng)計(jì)算與特性分析[J].西安交通大學(xué)學(xué)報(bào),2013,47(2):109-115.
[13] Yousfi M,Robin J P,Kanzari Z.Breakdown electric field calculations of hot SF6 for high voltage circuit breaker applications[J].IEEE Transactions on Dielectrics and Electrical Insulation,2005,12(6):1192-1200.
[14] Yousfi M,Robin J P,Kanzari Z.Electron-molecule collision cross sections needed for breakdown electric field calculations of hot dissociated SF6[J].Journal of Physics:Conference Seriess,2008,115(1):1-9.
[15] GB 1984—2003 高壓交流斷路器[S].